module SPECIFICATIONS
POWER
Module capacity - up to 250 kW
Individual rack capacity - up to 40 kW
DISTRIBUTION
There are four power distribution options:
bus bars, single feed per rack
bus bars, redundant A- and B-side feeds per rack
cable loom, single feed per racks
cable loom, redundant A- and B-side feeds per rack
COOLING
Direct evaporative system.
Rated equipment cooling from 70kW to 560 kW in 70 kW steps by adding 70 kW cooling units(N+1 configuration).
Nominal rated airflow for a single unit - 12,000 cubic metres per hour (full system - 96,000 cubic metres per hour)
Temperature, cold aisle - 24 celsius
Temperature, hot aisle - 39 celsius (deltaT = 15 celsius)
COMMS
Cable trays provided throughout, for both internal and customer use
SECURITY
Insert details here
FIRE DETECTION
VESDA
FIRE PREVENTION
Insert details here
FIRE SUPPRESSION
Argonite C60/IG-55 inert blend extinguishing agent, coincidence detection to extinguishant release, local and external 1st. stage and 2nd. stage alarms, high sensitivity FAAST smoke detection for early warning
[or similar - TBC]
MONITORING
Insert details here
SECURITY
Insert details here
MAINTENANCE
Insert details here
ENVIRONMENT
Insert details here
DIMENSIONS
Overall structure
Based on international standard high-cube shipping containers individual modules are: 8ft (2.43m) wide, 9.5ft (2.89m) ) high and come in two lengths; 20ft (6.06m) and 40ft (12.2m).
Any number of modules may be used.
Interior space
Length -
Width -
Height -
Cold chamber
Width -
Length -
Hot chamber
Width -
Length -
Exterior doors
Height -
Width -
WEIGHT
Unladen -
Fully laden -
RACKS
600 mm pitch
1200 mm (full) depth
48u
OPERATING ENVIRONMENT
Maximum operating temperature - ?
Maximum operating humidity - ?
ACCESS CONTROL
insert details here - do we leave this to clients to specify and just provide fixings for their systems?